Ambetronics

Home

Our Standard Certifications

Combustible Gas Detector – GT-4220-FLP

The Gas Leak Detector for Combustible Gases – GT-4220-FLP, a Flameproof and PESO Certified Smart Gas Detector/Transmitter, is meticulously crafted for swift and dependable detection of combustible gases. Leveraging Catalytic, Pellistor, or Semiconductor technology, it excels in identifying leaks of LPG, PNG, CNG, LNG, Natural Gas, and other flammable gases. The device features a digital display showcasing gas concentrations through a 7-Segment LED display, accompanied by four LEDs that provide a clear indication of the instrument’s status. It offers optional outputs including a standard 4-20mA signal output and three relay outputs with a rating of 5A at 250VAC/5A at 30VDC. Additionally, users have the flexibility to opt for an Isolated RS-485 Communication Port with MODBUS RTU Protocol for seamless integration into industrial systems. The programming is secured with a password, and users can change the password as needed. The Flameproof model facilitates non-intrusive programming using a Magnetic Wand. With the capability to detect gas concentrations down to %LEL, the device provides valuable indications for ‘Sensor Open,’ ‘Over Range,’ and ‘Temperature Alert,’ ensuring comprehensive monitoring and enhanced safety in industrial environments.

1. PESO-Certified Flameproof Enclosure:
– Gas Leak Detector for Combustible Gases Ensures safety in hazardous environments.
– Compliant with Ex d IIC T6 Gb standards (-25°C ≤ Ta ≤ +60°C).
– IP-68 protection for reliability.
2. Advanced Detection Technology:
– Gas Leak Detector for Combustible Gases Utilizes Catalytic, Pellistor, or Semiconductor technology.
– Fast and reliable response to combustible gas leaks.
– Suitable for LPG, PNG, CNG, LNG, Natural Gas, and flammable gases.
3. Isolated RS-485 Communication:
– Enables seamless integration into industrial systems.
– Follows MODBUS RTU protocol for efficient communication.
4. Non-Intrusive Programming:
– Configurable without opening the enclosure cover.
– Password-protected programming menu ensures security.
5. Alarm Relay Contacts:
– Two relay contacts for Warm, Alarm, and Fault conditions.
– Enhances real-time monitoring and response.
6. Inbuilt Temperature Detection:
– Monitors ambient temperature for additional safety.
– Alerts in case of temperature anomalies.=
7. Indicator LEDs:
– Displays ‘OPEN,’ ‘OVER,’ and ‘Temperature Alert’ (T-AL).
– Test Mode for checking electronics, including alarm LEDs and relays.
8. Flameproof Housing:
– Cast aluminum alloy cabinet with CIMFR approval.
– Double Compression Cable Gland for secure cable entry.
– Stopping Plug (M20 x 1.5P & M25 x 1.5P) for additional safety.
9. Wide Range of Applications:
– Suitable for gas metering, CNG stations, oil and gas industries, refineries, commercial kitchens, chemical plants, automotive, and more.

Technical Specifications:

1. Detection Principle:
– Catalytic, Pellistor, or Semiconductor technology.
2. Sensor Holder:
– SS 316 construction for durability.
3. Temperature Sensor:
– Measures ambient temperature for enhanced safety.
4. Detection Method:
– Continuous diffusion for consistent monitoring.
5. Accuracy:
– Catalytic/Pellistor: ±2% F.S.
– Semiconductor: ±10%.
6. Response Time:
– Less than 5 seconds for rapid detection.
7. Start-up Time:
– Less than 30 seconds for quick activation.
8. Electrical Specifications:
– Supply Voltage: 18 to 36 VDC (Typically 24VDC).
– Power Consumption: Less than 2 Watts.
9. Output Signal:
– Isolated RS-485 communication with MODBUS RTU protocol.
– Optional Two SPST NO/C relays (5A/250VAC, 5A/30VDC).
10. Environmental Conditions:
– Operating Temperature: -15 to +55°C.
– Storage Temperature: -10 to +60°C.
– Humidity: Less than 95% Non-Condensing.
11. Dimensions:
– 158 mm (H) x 199 mm (W) x 97 mm (D).
– Weight: Approx 1.25 kg.
12. Approvals and Compliance:
– PESO and CIMFR approved for flameproof enclosure.
– Compliant with IS/IEC 60079-0:2017, IS/IEC 60079-1:2014, IS/IEC 60079-31:2013, and IS/IEC 60529:2001 standards.
13. Accessories (Optional):
– Certified 24 VDC Power Supply.
– Canopy & Mounting Stand.
– RS-485 to USB Converter.
– Hooter cum Flasher.
14. Common Deliverables:
– Test Calibration Certificate.
– Reference Calibration Gas Certificate.
– Operational/Instrument User Manual.
– Standard Mounting Hardware.
– Protection Cap.
– Calibration Cap.
– Magnetic Wand.

Suitable for Gas Metering Skids and CNG Stations. Essential for Fertilizer Plants, Oil & Gas Industries, and Ambient Monitoring.
Ideal for Gas Pipeline Projects, Refineries, and Gas Metering Stations. Reliable for Gas Refilling Stations, BMS, and Commercial Kitchens.
Effective in Gas Manifold Areas and Chemical & Petrochemical Plants. Perfect for Automotive Industrial and Paint Shops, LPG Gas Cylinder Banks, and Sewage Plants.
Ideal for Burner and Furnace Areas, Heat Treatment Plants, and Chemical Storage Areas. Suitable for LPG Bullet Yards, Chemical Processing Plants, and Offshore Drilling Platforms.
Useful in Power and Industrial Plants.

Get Quote From Our Sales Team