The FLD-2211-FLP UV & Dual IR Flame Detector is a cutting-edge device designed for fire detection in various industrial applications. Its multi-spectral sensitivity, utilizing UV and IR sensors, ensures efficient detection of fires with a dual spectrum design for long-distance coverage and high immunity to false alarms. The detector offers sensitivity selection, allowing for zone-specific settings to prevent crossover detection. With high sensitivity and a rapid response time of less than 5 seconds, this detector can identify small and large flames over significant distances. It features multiple output options, including relays, 0-20mA, and 0-10V, and supports HART protocol for configuration. The device is user-programmable via Bluetooth, HART, or RS-485. In terms of approvals and compliance, the detector is certified for flameproof environments and adheres to relevant standards. It finds applications in diverse settings such as refineries, power plants, chemical plants, tunnels, storage tanks, engine rooms, aircraft hangars, military and marine applications, and more.

1. Multi-Spectral Sensitivity: UV & Dual IR Flame Detector utilizes UV and IR sensors for comprehensive fire detection by analyzing the multi-spectral sensitivity of flames.
2. Dual Spectrum Design: UV & Dual IR Flame Detector offers long-distance detection capabilities and higher immunity to false alarms, ensuring reliable performance in various industrial environments.
3. Sensitivity Selection: Allows users to configure sensitivity settings, preventing zone crossover detection and ensuring precise flame identification.
4. High Sensitivity and Fast Response: Combines high sensitivity with a response time of less than 5 seconds, ensuring rapid and accurate detection of both small and large flames over varying distances.
5. Dynamic Range: Accommodates the detection of flames, whether nearby or at a considerable distance, providing flexibility in different operational scenarios.
6. Multiple Output Options: Offers versatile output options including three relays for flame detection, auxiliary, and fault, as well as 0-20mA or 0-10V stepped signals. Supports HART protocol for configuration.
7. User Programmable: Configurable via Bluetooth, HART, or RS-485, providing flexibility in setup and adjustments.
8. Built-In Self-Test (BIT): Includes automatic self-check tests to ensure continuous reliability and functionality.
9. Optional Mobile Alerts: Provides mobile alerts via LoRa/WiFi for timely notifications and remote monitoring.
10. IoT Connectivity: Optional IoT connectivity for seamless integration into broader industrial monitoring systems.
11. Heat Detector Extension: Optional extension for heat detection, enhancing the range of hazards addressed.
12. Test Lamp Compatibility: Supports safe testing using compatible test lamps.

Technical Specifications:

1. Parameter Setting: Field configuration settings facilitated through Bluetooth or MODBUS RTU Protocol.
2. Spectral Response:
– UV Band: 185nm to 260nm
– Two IR Bands: 3000nm to 5000nm
3. Detection Range:
– n-Heptane: 88ft (27m)
– Kerosene: 82ft (25m)
– Diesel Fuel: 82ft (25m)
– Methanol: 66ft (20m)
– Gasoline: 82ft (25m)
4. Response Time: Typically less than 5 seconds (Depending on Flame Size & Sensitivity).
5. Field of View: 90° Horizontal, 90° Vertical.
6. Adjustable Time Delay: Up to 30 seconds.
7. Adjustable Sensitivity: Low, Medium, and High settings.
8. Power Supply: 18 to 36 VDC, typically 24VDC. Power consumption less than 3W.
9. Output Signals:
– 4-20mA Current Output
– 0-10V Output
– LED Indicators for Power, Fire Detection, and Communication.
10. Relay Outputs: Three SPDT relays (5A@30VDC & 250VAC) for Fail-Safe, Fire Detection, and Auxiliary functions.
11. Communication Protocols:
– RS-485 with MODBUS RTU Protocol
– Optional HART Protocol
12. Environmental Conditions:
– Operating Temperature: -15°C to +50°C
– Storage Temperature: -20°C to +85°C
– Humidity: Less than 95% Non-Condensing
13. Flameproof Housing:
– Degree of Protection Class: IP66 & IP68
– Housing Material: Cast Aluminium LM6 alloy or Stainless Steel
– Cable Entry: Flameproof, IP66 Double Compression Cable Gland – M20 x 1.5 (P)
14. Mounting Options: Wall or Pipe Mounting.
15. Weight:
– IIC Enclosure: Approx 2.53 Kg. (LM6), Approx 7 Kg. (SS316)
– JB-90 Enclosure: Approx 1.25 Kg. (LM6), Approx 4.5 Kg. (SS316)
16. CIMFR & PESO Approvals:
– Degree of Protection Class: IP66 & IP68
– Certified to Ex d IIC T6 Gb, @ 60°C IP68
– Standard Compliance: IS/IEC 60079-0:2017, IS/IEC 60079-1:2014, IS/IEC 60529:2001
– BIS License Number: 7800046916 P538850/8, Dt.: 16/06/2022

Refineries Flame detection in refining processes
Power Plants Ensuring safety in power generation
Chemical Plants Monitoring for potential fire hazards
Tunnels Detecting flames in enclosed spaces
Storage Tanks Safeguarding against tank-related fires
Engine Rooms Ensuring safety in engine compartments
Aircraft Hangars Flame detection in aviation facilities
Military Applications Protecting military installations
Marine Applications Fire safety measures on marine vessels
Petrochemical / LNG/LPG Prod Detecting flames in petrochemical plants
Waste Recycling Ensuring safety in recycling processes
Pharmaceutical Production Flame detection in pharmaceutical plants

Get Quote From Our Sales Team