Our Standard Certifications
UV Flame (Radiant Energy) Detector – FLD-0011-FLP
The FLD-0011-FLP UV Flame Detector is a high-performance device designed for the detection of flames in various industrial environments. Utilizing UV sensors, this detector offers multi-spectral sensitivity to efficiently identify fires. With a line of sight visual range, it ensures effective detection within specific distances. The UV Sensor design enhances detection capabilities for long distances while minimizing false alarms. Featuring sensitivity selection and high sensitivity combined with a fast response time, the detector ensures rapid and accurate flame detection. Its high dynamic range enables the identification of both small and large flames over varying distances. The device offers multiple output options, including relays for flame detection, auxiliary functions, and fault indication. It supports 0-20mA or 0-10V output, with optional HART protocol for configuration settings, and is RS-485 and MODBUS compatible. The detector supports user programmability via Bluetooth, HART, or RS-485, and includes optional features like heat detector extension, date-time stamped event logging, built-in self-test (BIT), mobile alert (LoRa/WiFi), and IoT connectivity. It is suitable for a range of applications, including cold storages, laboratories, warehouses, and indoor chemical storage.
1. Multi-Spectral Sensitivity: Single UV Flame Detector detects fires using UV sensors, providing comprehensive flame detection.
2. Line of Sight Visual Range: Single UV Flame Detector offers a clear line of sight within specified distances for effective flame monitoring.
3. Sensitivity Selection: Allows users to customize sensitivity settings, minimizing the risk of zone crossover detection.
4. High Sensitivity and Fast Response Time: Ensures rapid and accurate flame detection, suitable for both small and large flames.
5. Dynamic Range: Capable of detecting flames nearby or over large distances, providing flexibility in various applications.
6. Multiple Output Options: Offers flexibility with three relays for flame detection, auxiliary functions, and fault indication.
7. Analog Output Options: Supports 0-20mA or 0-10V output for compatibility with different systems.
8. Optional HART Protocol: Enables configuration settings through the HART protocol, enhancing versatility.
9. RS-485 and MODBUS Compatibility: Facilitates easy integration into existing systems with widely used communication protocols.
10. User Programmable: Configurable via Bluetooth, HART, or RS-485, allowing users to adapt the device to specific requirements.
11. Optional Features for Enhanced Functionality:
– Heat detector extension
– Date-time stamped event logging
– Built-in self-test (BIT)
– Mobile alert (LoRa/WiFi)
– IoT connectivity
Technical Specifications:
1. Parameter Setting: Configurable in the field using Bluetooth or MODBUS RTU Protocol.
2. Spectral Response: UV Band (185nm to 260 nm).
3. Detection Range:
– n-Heptane: 88ft (27m)
– Kerosene: 82ft (25m)
– Diesel Fuel: 82ft (25m)
– Methanol: 66ft (20m)
– Gasoline: 82ft (25m)
4. Performance:
– Response Time: Less than 5 seconds
– Field of View: 90° Horizontal, 90° Vertical
– Adjustable Time Delay: Up to 30 seconds
– Adjustable Sensitivity: Low, Medium, and High
– BIT: Automatic self-check test
– Performance Test: Can be tested using Test Lamp (F TU-3311) for safe testing.
5. Electrical:
– Supply Voltage: 18 to 36 VDC (typically 24VDC)
– Power Consumption: Less than 3W
6. Output Signal:
– 4-20mA Current Output or 0-10V
– L.E.D. Indication: Power LED (Green), Fire Detect LED (Red), Communication LED (Blue)
– Three SPDT relays for Fail-safe, Fire Detection, and Auxiliary output.
7. Environmental:
– Operating Temperature: -15°C to +50°C
– Storage Temperature: -20°C to +85°C
– Humidity: Less than 95% Non-Condensing
8. Flameproof Housing:
– Degree of Protection Class: IP-66 & IP-68
– Housing Material: Cast Aluminium LM6 alloy or Stainless Steel
– Cable Entry: Flameproof, IP66
9. Accessories (Optional):
– RS-485 to USB or RS-232 converter
– Hooter cum Flasher
– Protection Cover
– Heat Detector
– Air Shield
– Magnetic Wand
– Test Lamp
10. CIMFR & PESO Approvals & Standards: Certified to Ex d IIC T6 Gb, complying with IS/IEC standards and holding relevant approvals from CIMFR and PESO.
Cold Storages | Fume Hoods |
Heating Rooms For Chemicals | Indoor Hydrogen Storage & Processing |
Radio Amplifier Rooms / Isolators For Antennas | Suitable For Indoor Applications |
Battery Storage Rooms / Data Communication | Laboratories |
Indoor Chemical, Fuel & Solvent Storage | Warehouses |